LinksThermal UnitsMSDS Fixed System FAQ |
PDFsMSDSData Sheet Specifications FAQs |
Due to their fast response time, low fire extinguishing concentration, and environmental safety, Stat-X fire suppression systems may be used in critical applications across a wide range of industries. Aerosol generators are suitable for use in:
In the event of a fire, Stat-X generators can be activated either manually or automatically via the integrated thermal detector.
Upon activation, the generators produce an exceptionally effective, ultra-fine, potassium based aerosol. Unlike gaseous systems, Stat-X aerosol generators are very cost effective to install and maintain — as they do not require the pressure vessels, piping or expensive installation costs associated with other extinguishing systems.
Space and weight requirements are minimal and, in many applications, the small size of the Stat-X aerosol generators makes them the only viable option. On an agent weight basis, Stat-X aerosol is ten times more effective than gaseous agent alternatives.
Fire suppression is rapidly achieved through interference between the ultra-fine aerosol particulate and the flame's free radicals — terminating propagation of the fire.
Stat-X aerosol generators are virtually maintenance free and have a shelf life of over 10 years. This, coupled to their very low installation cost, makes them an extremely cost effective fire protection solution.
Agent Container. The generator housing shall be constructed of exterior and interior stainless steel shells separated by an insulating material. Top and bottom of housing shall be stainless steel and (for electrically activated units) incorporate a ¾" NPT fitting to enable direct connection to conduit. Housing shall be sealed with a non-permeable membrane and shall incorporate a mechanical means to insure rupture of the membrane upon activation. Housing shall be non-pressurized prior to system activation.
Finish. Brushed Stainless Steel.
Aerosol Agent. Aerosol generated shall be potassium based and manufacturer shall provide fifteen (15) minute time weighted average data from an independent United States laboratory demonstrating that the aerosol does not produce (at normal design concentrations harmful levels of CO, CO2, and NOx based on NIOSH standards. Shall have no ozone depletion potential and no global warming potential. Agent shall be approved for commercial sale by the US EPA.
Thermal Actuator. Unit shall be activated by means of a thermal actuation device rated 70°C, 95°C, or 123°C. Actuator shall be anodized aluminum or stainless steel and shall be capable of both thermal and/or manual activation.
Operation/Storage Parameters:
Transportation Classification:
General Specifications:
| Model | 30 T | 60 T | 100 T | 250 T | 500 T |
| Aerosol Mass kg (lbs) |
.03 (.07) |
.06 (.14) |
.10 (.22) |
.25 (.55) |
.50 (1.10) |
| Ship. Wt./unit packaging kg (lbs) |
0.26 (.60) |
0.35 (.80) |
1.44 (3.20) |
2.72 (6.00) |
3.63 (8.00) |
| Length (with actuator) mm (inches) |
109 (4.30) |
142 (5.60) |
152 (6.00) |
168 (6.60) |
218 (8.60) |
| Diameter mm (inches) |
51 (2.00) |
51 (2.00) |
76 (3.00) |
127 (5.00) |
127 (5.00) |
| Discharge Time (sec) | 8.0 | 16.0 | 12.0 | 12.0 | 23.0 |
| Activation Temperature Options | 70°C (158°F) |
95°C (203°F) |
123°C (254°F) |
||
| Part Number (Order separately from unit) | 14650 | 14651 | 14652 | ||
| Model | Part Number | Aerosol Mass (grams) | Maximum Volume Coverage | Maximum Area Coverage | Maximum Mounting Height | |||
| (m3) | (ft3) | (m2) | (ft2) | (m) | (ft) | |||
| 30 T | 15300 | 30 | 0.50 | 17.66 | 1.50 | 16.0 | 2.0 | 7.0 |
| 60 T | 15310 | 60 | 1.00 | 35.32 | 2.82 | 30.3 | 2.5 | 8.0 |
| 100 T | 15410 | 100 | 1.62 | 57.21 | 4.75 | 51.8 | 2.5 | 8.0 |
| 250 T | 15510 | 250 | 4.04 | 142.7 | 11.9 | 128.0 | 3.0 | 10.0 |
| 500 T | 15610 | 500 | 8.08 | 285.3 | 23.8 | 256.0 | 3.0 | 10.0 |