LATEX FIRE RETARDANT INTUMESCENT COATING
Data Sheet
Back To Top - Download PDF
Description
Guardian is a quick-drying, latex flat finish, Type Class-A fire retardant coating designed for use on interior surfaces. When it comes in contact with heat or fire, Guardian intumesces to form a thick protective blanket between the fire and the substrate to which it is applied. Guardian works by reducing the surface burning characteristics of the substrate to retard the spread of flame.
Applications
Guardian is ideally suited for a variety of commercial and institutional facilities, particularly where occupants need additional time to evacuate the building or relocated to other areas. These applications include hospitals, nursing homes, correctional facilities, day care centers, schools and restaurants. Guardian is also recommended for areas containing valuable or irreplaceable contents including museums, rare book rooms, art galleries, data centers, recording studios and telecommunications complexes.
Features
- Inhibits the spread of flames in all types of occupancies
- U.L.-listed for Class A flame spread retardance
- Offered in a range of custom colors to match any decor
- Goes on quickly and smoothly with ordinary brush, roller or sprayer
- Requires only soap and warm water for post-application cleanup
- Contains no lead, mercury or chromate hazardous compounds
- Provides optimum fire retardance with two coats – no preliminary or overcoats required
- Available in one- and five-gallon containers
Performance Standard
Guardian has been tested by independent laboratories and testing services in accordance with ASTM E-84 – Surface Burning Characteristics of Building Materials – per the National Fire Protection Association (NFPA) Life Safety Code 101, Section 6.5.3 – Interior Wall and Ceiling Finish.
| Testing Agency |
Test |
Flame Spread |
Smoke Development |
| Underwriters Laboratories |
ASTM E-84 |
18.4 |
39.5 |
| SGS U.S. Testing Company |
ASTM E-84-98 |
15.0 |
125.0 |
| Intertek Testing Services |
ASTM E-84-01 |
10.0 |
5.0 |
Hardwood Plywood & Veneer
Association (HPVA) Lab &
Testing Services |
ASTM E-84
Tunnel Furnace |
5.0 |
5.0 |
| Govmark |
UBC 42-2 |
No Ignition
in 2 Minutes
No Ignition
in 4 Minutes |
|
|
Call to discuss your specific requirements with one of our professionals.
Specifications
Back To Top - Download PDF
Product Description. Paint shall be UL listed, water based intumescent type, Class-A Fire Retardant Coating, designed for use on interior surfaces and tested to ASTM E-84. It shall be quick drying, with a flat finish that will reduce the surface burning characteristics of the substrate. When heat or flame is present, the coating will intumesce, forming a thick protective blanket between the fire and substrate, reducing the flame spread.
Shelf Life. Paint shall have a shelf life of 1 year
Coverage. The paint shall have a minimum coverage of 175 square feet per gallon
Viscosity. The paint shall have a viscosity of 90-120
Packaging. The paint shall be packaged in one and five gallon pails.
Origin. Shall be manufactured in the U.S.A.
Material safety data sheet
Back To Top - Download PDF
MSDS# 002
DATE: 08/06
For information only, call 1-952-935-9745. For emergencies,
call CHEMTREC: DOMESTIC NORTH AMERICA 800-424-9300
INTERNATIONAL, CALL 703-527-3887
GUARDIAN – LATEX FIRE RETARDANT INTUMESCENT COATING
SECTION I – HAZARDOUS INGREDIENTS
PRODUCT IS NON-HAZARDOUS ACCORDING TO OSHA HAZARDOUS
COMMUNICATION STANDARD 190.1200. THIS PRODUCT DOES NOT CONTAIN
TOXIC CHEMICALS SUBJECT TO REPORTING REQUIREMENTS OF SECTION 313
OF THE EMERGENCY PLANNING AND COMMUNITY RIGHT TO KNOW ACT OF 1986
AND OF 40 CFR. |
|
SECTION II – PHYSICAL DATA
BOILING RANGE – 212° F (WATER)
% VOLATILE VOLUME -N/A
WEIGHT/GAL -11-12 LBS.
EVAPORATION RATE -: SLOWER THAN ETHER
VAPOR. DENSITY -N/A |
|
SECTION III -FIRE AND EXPLOSION HAZARD DATA
FLAMMABILITY CLASSIFICATION: NOT FLAMMABLE
UNUSUAL FIRE AND EXPLOSION HAZARDS: CLOSED CONTAINERS MAY EXPLODE
DUE TO A BUILD UP OF STEAM PRESSURE WHEN EXPOSED TO EXTREME HEAT.
SPECIAL FIRE FIGHTING PROCEDURES: N/A |
|
SECTION IV – HEALTH HAZARD DATA
EFFECTS OF OVER EXPOSURE: ACUTE HYPERSENSITIVE INDIVIDUALS MAY
EXPERIENCE SOME SKIN SENSITIZATION OR IRRITATION.
CHRONIC: NONE KNOWN
MEDICAL CONDITIONS PRONE TO AGGRAVATION BY EXPOSURE: NONE KNOWN
PRIMARY ROUTES OF ENTRY: DERMAL (X) INHALATION ( ) INGESTION (X)
EMERGENCY & FIRST AID PROCEDURES: EYES: FLUSH IMMEDIATELY WITH LARGE
AMOUNT OF WATER FOR 15 MINUTES. TAKE TO PHYSICIAN FOR MEDICAL
TREATMENT.
SKIN: WASH AFFECTED AREAS WITH SOAP & WATER. CONSULT PHYSICIAN IF
IRRITATION PERSISTS;
INGESTION: DRINK 1 OR 2 GLASSES OF WATER TO DILUTE. DO NOT INDUCE
VOMITING. CONSULT PHYSICIAN IMMEDIATELY. |
|
SECTION V – REACTIVITY DATA
STABILITY: UNSTABLE ( ) STABLE (X)
HAZARDOUS POLYMERIZATION: MAY OCCUR ( ) WILL NOT OCCUR (X)
HAZARDOUS DECOMPOSITION PRODUCTS: OXIDES OF CARBON
CONDITIONS TO AVOID: N/A |
|
SECTION VI – SPILL OR LEAK PROCEDURES
STEPS TO BE TAKEN IN CASE MATERIAL IS RELEASED OR SPILLED:
USE ABSORBENT MATERIAL SUCH AS SAND TO PICK UP EXCESS
WASH AREA WITH SOAP AND WATER.
WASTE DISPOSAL METHOD: DISPOSE OF ACCORDING TO LOCALSTATE AND
FEDERAL REGULATIONS.
BEFORE ATTEMPTING CLEAN UP REFER TO HAZARD CAUTION INFORMATION IN
OTHER SECTIONS OF THIS SHEET. |
|
SECTION VII – SAFE HANDLING & USE INFORMATION
RESPIRATORY PROTECTION: NONE REQUIRED
VENTILATION: OPEN WINDOW
PROTECTIVE GLOVES: NONE REQUIRED
EYE PROTECTION: WEAR SAFETY GLASSES
OTHER PROTECTIVE EQUIPMENT: FULL LENGTH CLOTHING TO AVOID
PROLONGED & REPEATED CONTACT |
|
SECTION VIII – SPECIAL PRECAUTIONS
PRECAUTIONS TO BE TAKEN IN HANDLING AND STORING: STORE CONTAINERS
BETWEEN 40 AND 100 Deg. F. PROTECT FROM FREEZING.
OTHER PRECAUTIONS: NONE |
|
Frequently Asked Questions
Back To Top - Download PDF
WHAT IS GUARDIAN PAINT ?
Guardian paint is non-toxic water based intumescent latex paint that expands when exposed to direct flame, forming a "char barrier" that lifts off the substrate, providing an effective and durable barrier that cuts off the fuel source a fire needs to develop. Guardian paint will prohibit flashovers when used on ceilings and walls; its intumescent composition affords an insulating barrier against fire spread.
WHERE WOULD I TYPICALLY USE IT?
Guardian paint may be used across a broad spectrum of industrial, commercial, marine, and residential applications. It can be applied to virtually any substrate except structural steel.
Commercial and Industrial applications include office complexes, hotel rooms, parking garages, flammable material storage, furnace rooms, UPS and telecom rooms, switchgear rooms, server rooms, document storage areas, or any other area where fire hazards exist
Guardian paint is also excellent as protection on the insides of boats - especially engine rooms.
It may be used in residential locations in areas such as kitchens, playrooms, furnace rooms, and garages.
HOW DO I APPLY GUARDIAN PAINT?
Guardian paint is a water based latex paint that is applied like any other latex paint i.e., with brushes, rollers or spray. It should never be applied in high humidity areas or when the ambient temperature is below 40° F. It cleans up readily with soap and water. Guardian paint should never be diluted.
DOES GUARDIAN PAINT CURRENTLY HAVE ANY APPROVALS?
Guardian is UL approved, New York City Housing Authority approved, ASTM E84-01.
WHY IS GUARDIAN PAINT UNIQUE?
Guardian paint is unique in that it is a water-based, non-toxic paint which has a zero flame spread. The proprietary formula enables it to also insulate the substrate which means it will not allow the transfer of all the heat to the substrate.
HOW EXPENSIVE IS GUARDIAN PAINT IN COMPARISON TO OTHER LATEX PAINTS?
Guardian paint is price compatible with a good quality latex paint Guardian does everything that a good paint does EXCEPT BURN.
CAN I USE GUARDIAN PAINT ON STRUCTURAL STEEL?
Guardian paint can be used on almost any surface, i.e., wood, corrugated steel, wallboard, etc. However, Guardian paint alone CANNOT be used on structural steel. To get any performance on structural steel you would have to box the steel with sheetrock then paint it with Guardian paint.
WHERE CAN I BUY GUARDIAN PAINT?
Contact info@statx.com to find the location of your nearest Guardian distributor.
HOW DO I PREPARE THE SURFACE BEFORE APPLYING GUARDIAN PAINT?
As with any paint, the surface must be clean, smooth and free from any loose particles. If you are applying Guardian paint on any exceptionally glossy surface or composite material, a primer may be required.
IS GUARDIAN PAINT HAZARDOUS?
Guardian paint is non-toxic and is not hazardous to humans, animals or to the environment.
WHAT IS THE SHELF LIFE?
Guardian should be applied within one year of delivery.
HOW LONG DOES GUARDIAN PAINT LAST ONCE IT IS APPLIED?
It will last as long as the paint adheres to the substrate and is not damaged or penetrated.
CAN IT BE EFFECTIVE IF USED AS A PRIMER?
Yes.
IS GUARDIAN PAINT AVAILABLE IN A GLOSSY FINISH? OR CLEAR?
No. Guardian is only available in flat finish. The base color of Guardian paint is white but it can be tinted to virtually any color. It is not available as a clear coat.
WHAT DOES INTUMESCENT MEAN?
When an intumescent paint is exposed to temperatures of 375° F it expands up to 20 to 100 times its own thickness.
DOES IT INSULATE WHEN IT EXPANDS?
Unlike other intumescent paints, Guardian does insulate the substrate when it expands.
CAN GUARDIAN PAINT BE USED ON EXTERIOR APPLICATIONS?
Yes, if an exterior topcoat is applied.
WILL GUARDIAN PAINT PROVIDE PROTECTION IF APPLIED ON WIRES OR PVC WHICH GIVE OFF TOXIC MATERIAL WHEN BURNING?
Yes, Guardian paint will protect wires and PVC and prevent them from burning in a fire.
HOW CAN I CONFIRM THAT THE COATING HAS BEEN APPLIED CORRECTLY?
Determine the total square feet of area to be coated and divide this by the required square feet per gallon (spread rate) as indicated on label, to obtain the number of gallons required. |