WHAT IS A Stat-X AEROSOL GENERATOR?

An aerosol generator is a self contained extinguishing unit that contains an aerosol forming compound which, during a controlled combustion process within the generator, produces an ultra-fine aerosol extinguishing agent that is significantly more effective than currently available alternatives. The units are constructed of stainless steel components, are listed for both area and volumetric coverage, and require no piping, nozzles, or other distribution equipment. In effect, the generator acts as its own storage, production and delivery device.

ARE THE AEROSOL GENERATORS RE-CHARGEABLE AFTER DISCHARGE?

No. The units are designed for single use only. After discharge turn around time is minimized as re-connection of a new generator is quickly and easily accomplished.

HOW DOES IT WORK?

A highly stable solid charge of the aerosol forming composition is contained within the sealed generator. Upon activation of the initiator, the charge begins a controlled burn producing an ultra-fine aerosol, which is ten times as effective as any agent currently on the market. The effective aerosol passes through a series of oxidation and cooling filters, where the temperature of the aerosol is rapidly reduced before it escapes through the discharge ports of the generator at low pressure. Generator placement within the hazard area provides proper flow and distribution of the highly effective aerosol within the protected volume.

DOES IT REDUCE THE OXYGEN LEVEL?

No, oxygen levels are not affected.

HOW DOES IT EXTINGUISH FIRES?

Unlike other agents that work by reducing oxygen levels or by cooling, the aerosol extinguishes by chemical interaction with the free radicals that fuel the growth of the fire – in the same manner as halon did. The aerosol stream contains ultra-fine (1-2 micron)particles of potassium compounds that provide a large surface area interaction with the fire. In the fire zone the free potassium radicals bind with the free radicals of the fire (O, OH, H) to rapidly slow and extinguish the fire.

HOW EFFECTIVE IS IT?

Stat-X is extremely effective. Tests on class B fires have shown it to be 5 times more effective than halon and 10+ times more effective than currently available halon alternatives. This dramatically reduces weight and space requirements.

WHERE CAN IT BE USED?

Stat-X is an aerosol and shares many of the flow characteristics of a gas. It is suitable for use in un-occupied and normally un-occupied enclosed volumes and has the added advantages of extended hold times and less susceptibility to leakage. In addition, Unlike HFC's, which can break down and produce deleterious compounds such as hydrofluoric acid when exposed to elevated temperatures, Stat-X does not break down when exposed to a fire.

IS IT SAFE FOR THE ENVIRONMENT?

Yes. Stat-X has no global warming potential and no ozone depletion potential.

IS IT APPROVED BY THE EPA?

Yes. Stat-X has been approved for sale and use in un-occupied and normally un-occupied spaces by the United States Environmental Protection Agency.

IS IT SAFE FOR SENSITIVE EQUIPMENT?

Stat-X aerosol has been tested on a wide range of materials including structural, aviation composites, and materials commonly used in electronics, and circuit boards. In all cases it has been shown that Stat-X has no deleterious effect on the operating capability of equipment.

Due to the ultra-fine particle size and the method of generation, the particulate is quite buoyant and suspends in the gas/air mixture within the protected enclosure. Because of this “buoyant” effect the aerosol does not begin to “settle” for an extended period and, therefore, is extremely easy to vent from the protected area. Only very minor amounts of particulate may be deposited on equipment and, generally, there is no need to do anything beyond extraction of the air within the protected volume through a fan or air handling system – followed by a blow down with compressed air. Any particulate deposited on horizontal surfaces will be = 2µm and will not form a continuous layer. Large gaps will exist between particles - leaving no potential for electrical conductivity issues to develop.

As a precautionary measure, however, it is always good practice to inspect and clean the site thoroughly following a discharge. While the aerosol itself is quite “clean”, environmental factors are also a consideration. The unknown, and potentially harmful, by-products of an actual fire pose the biggest risk to sensitive electronic equipment. Because unknown products from the fire itself may be present, it is always recommended that equipment be blown down with air or vacuumed following a discharge to insure that no unwanted byproducts from the fire itself are present.

IS IT SAFE FOR PERSONNEL?

The aerosol, itself, consists of solid and gas combustion products. The solid phase is composed of highly dispersed particles that present insignificant health hazards for humans at normal design concentrations. The gas phase may contain very small amounts of carbon monoxide CO, carbon dioxide CO 2 , nitrogen oxides NO x , and ammonia NH 3 . Production of these gases is minimal in the case of Stat-X due to its patented construction, chemical formulation, and its manufacture in the United States using only technical and reagent grade chemicals. In tests conducted by a certified, accredited testing facility in the United States, Stat-X generators were shown to produce gas levels several orders of magnitude less than the standard allowed for automobile airbag systems for passenger vehicles.

While the components of the aerosol are not considered toxic at normal concentration levels, ingestion of the ultra-fine particulate may cause short-term discomfort and unnecessary exposure should be avoided. Exposure to the aerosol is generally of less concern than is exposure to the decomposition products of a fire. Accidental exposures under ten minutes are normally considered safe. There is a high obscuration factor with the aerosol and a 30 second time delay and system lock out switch should be used whenever personnel may be present in the protected space.

IS IT A CLEAN AGENT?

The term “clean agent” has traditionally referred to gases. The term itself is inaccurate as all agents may pose post discharge issues. The Stat-X aerosol does contain ultra-fine suspended particulate which is very buoyant and hangs in suspension for extended periods. Because of this, settling is minimal and removal of the aerosol can be accomplished easily by venting. While the aerosol itself is quite “clean”, environmental factors are also a consideration. The unknown, and potentially harmful, by-products of an actual fire pose the biggest risk to sensitive equipment.

Because unknown products from the fire itself may be present or because of unwanted environmental conditions, it is always recommended that the area is thoroughly cleaned to insure that no unwanted products are present. For example, on site maintenance and housekeeping may have been lax allowing accumulation of dirt in the enclosure. During discharge, any dirt within the enclosure will be blown around and then deposited as unwanted residue throughout the area.

Also, in rare cases, unit orientation may have been altered improperly or equipment may have been re-oriented within the protected enclosure resulting in an improper discharge directly onto a wall or equipment surface. This could result in the deposit of small, localized areas of highly concentrated agglomerated particulate on that surface. If left untended, an agglomerated mass may take on moisture and may cause non-progressive surface discoloration (copper,bronze) of unprotected metal surfaces. It is therefore, important that any agglomerated particulate be cleaned up with a water/alcohol solution no later than 24 hours following a discharge.

HOW IS A SYSTEM DESIGNED?

Stat-X are designed by trained, certified, and authorized distributors using a computer aided design program that uses data on dimensions, areas of leakage and location of uncloseable openings, fire class, and other factors to arrive at a system tailored to the clients specific requirements.

The design methods of calculation are part of our listing.

WHAT ARE THE SPACE REQUIREMENTS?

The generators are small, self-contained, and mounted at ceiling height. They do not take up valuable floor space as conventional systems do.

IS A Stat-X SYSTEM EXPENSIVE?

No. Stat-X systems are extremely cost effective. While actual costs will vary based on the size of the enclosure, leakage, and class of hazard, in general, an installed system will be significantly less expensive than alternatives. This is due to the small amount of agent required and the fact that installation costs are dramatically reduced because of the elimination of distribution manifolds, piping, and nozzles. Stat-X thermal units, where appropriate further reduce costs due to the elimination of detection and releasing devices.

WHAT IS THE SERVICE LIFE?

The service life of Stat-X generators is 10 years+.

WHAT IS A Stat-X THERMAL UNIT?

Stat-X thermal units are suitable for small enclosed spaces such as electronic enclosure, hazmat storage, switchgear cabinets, etc. The units are self contained and utilize a patented thermal detector that is integral to the generator – eliminating the need for ancillary detection and releasing devices. Units are available in several temperature settings to insure applicability to the hazard being protected.

WHAT ARE TYPICAL APPLICATIONS?

• Telecommunications Facilities
• Process Control Rooms
• Marine Engine Rooms
• High Value Mobile Equipment
• High Value Industrial Equipment Areas
• Flammable Liquid Storage Areas
• Data Processing Facilities
• Mining• Power Plants
• CNC machines

WHAT ABOUT MAINTENANCE COSTS?

Maintenance costs related to the generators themselves are minimal and involve only periodic visual examination of the generators and protected space to insure that the generators have not been damaged and that the system installation and space remains in the same configuration as that originally designed. Electrically activated systems require a regular check of the detection and control system, including all ancillary devices.

IS THERE AN NFPA STANDARD FOR AEROSOL EXTINGUISHING SYSTEMS?

Yes. The aerosol extinguishing systems are covered by NFPA 2010 Standard on Aerosol Fire-Extinguishing Systems, 2006 Edition.

DOES Stat-X HAVE ANY LISTING OR APPROVALS?

Yes. Stat-X is listed by Underwriter's Laboratories of Canada (ULC) to UL 2127 and has been approved by the Maritime and Coast Guard Agency (MCA) in the UK for use on marine machinery spaces on vessels up to 24m load line length. In addition, it has been approved for sale by the local AHJ in many areas of the world including Asia, the Pacific Rim, the Middle East, South and Central America, Europe, the United States, and Canada. Other listings around the world are currently in process and will be completed shortly.

HAVE Stat-X SYSTEMS PUT OUT FIRES IN THE REAL WORLD?

Yes. We have had a number of very successful incidents particularly with CNC machines where a relatively small investment in a Stat-X system has saved high value ($250K - $500k) equipment with very minimal downtime.

WHAT ABOUT MAINTENANCE COSTS?

Maintenance costs related to the generators themselves are minimal and involve only periodic visual examination of the generators and protected space to insure that the generators have not been damaged and that the system installation and space remains in the same configuration as that originally designed. Electrically activated systems require a regular check of the detection and control system, including all ancillary devices.

IS THERE AN NFPA STANDARD FOR AEROSOL EXTINGUISHING SYSTEMS?

Yes. The aerosol extinguishing systems are covered by NFPA 2010 Standard on Aerosol Fire-Extinguishing Systems, 2006 Edition.

DOES Stat-X HAVE ANY LISTING OR APPROVALS?

Yes. Stat-X is listed by Underwriter's Laboratories of Canada (ULC) to UL 2127 and has been approved by the Maritime and Coast Guard Agency (MCA) in the UK for use on marine machinery spaces on vessels up to 24m load line length. In addition, it has been approved for sale by the local AHJ in many areas of the world including Asia, the Pacific Rim, the Middle East, South and Central America, Europe, the United States, and Canada. Other listings around the world are currently in process and will be completed shortly.

HAVE Stat-X SYSTEMS PUT OUT FIRES IN THE REAL WORLD?

Yes. We have had a number of very successful incidents particularly with CNC machines where a relatively small investment in a Stat-X system has saved high value ($250K - $500k) equipment with very minimal downtime.

Material Safety Data Sheet

Download PDF

MSDS# 001
DATE: 01/06
For information only, call 1-952-935-9745. For emergencies, call CHEMTREC: DOMESTIC NORTH AMERICA 800-424-9300 INTERNATIONAL 703-527-3887 (COLLECT).

1. PRODUCT

Stat-X Solid Aerosol Generators - Models 30 thru 2500.

2. COMPOSITION/INFORMATION ON INGREDIENTS


Components – Chemical
(Hazardous Components = 1%)
      CAS#       COMMENTS:
Potassium Nitrate 7757-79-1 Components are blended and pressed into a highly stable, molded form. Molded composition is contained within a sealed double-walled stainless steel housing – no environmental exposure.
DCDA
461-58-5
Organic Resin 9003-35-4
Appearance & Odor: Beige to white in color. No odor.
Auto-Ignition Temperature: 300°C
Solubility in Water: Slightly Soluble

3. HAZARD IDENTIFICATION

Possible exposure to aerosol suppression agent if generator is activated. May cause temporary, mild irritation of mucous membrane if inhaled.

4. FIRST AID MEASURES

Contact Method: Procedure:
Inhalation Remove to fresh air
Eye Contact Flush with water
Skin Contact Wash with soap and water.
Ingestion Not a likely route of exposure.
Seek medical attention for further treatment, observation, and support if necessary.

5. FIRE FIGHTING MEASURES


In the event of a fire, evacuate the area and inform emergency services. Ignition of Stat-X produces a fire-suppression aerosol. Water may be used as an additional suppression agent.

6. ACCIDENTAL RELEASE MEASURES


If these devices are spilled they can be safely recovered by hand and should be inspected for damage prior to repacking. Suspect or damaged articles should be labeled and consigned for correct destruction.

7. HANDLING AND STORAGE


Store in temperate conditions. Avoid shock, electric currents, static discharge, excessive heat and extended periods of storage at temperatures greater than 65 °C.

8. EXPOSURE CONTROL/PERSONAL PROTECTION


Respiratory Protection Ventilate area completely after discharge. Do not enter area prior to complete venting of enclosure. Use filter mask as necessary during clean-up.
Hand Protection Wear gloves if handling generators prior to cooling.
Eye Protection Safety glasses are advisable.
Skin Protection N/A

9. PHYSICAL AND CHEMICAL PROPERTIES


Appearance: Stainless Steel Cylinder up to 270 mm in length

10. STABILITY AND REACTIVITY

These devices are extremely stable below 125°C. They should be protected from fire, sources of electrical power, shock, and high temperatures.

11. TOXOCOLOGICAL INFORMATION

Toxic by-products of combustion are extremely low. Main by-products are listed below with 15-minute TWA values for a maximum 100g/m3 concentration in a hermetically sealed volume.
Gas 15 minute Time Weighted Average in parts per million
NO 2 1.08
NO 0.97
CO 84.20

12. ECOLOGICAL INFORMATION

These devices are sealed and present no ecological hazards. The aerosol produced upon ignition has no global warming potential and an ozone depletion potential = 0.

13. DISPOSAL CONSIDERATIONS

Comply with all local, state, and federal/international regulations.

14. TRANSPORT INFORMATION

UN Number: 0432 Shipping Limitations:
UN Classification: 1.4 S Articles, Pyrotechnic for Technical Purposes Cargo Air Max single packaging – 100 kgs.
Packaging Group: II
Passenger Air Max single packaging - 25 kgs.
Division 1.4 S articles present no significant hazard as packaged for transport.

15. REGULATORY INFORMATION

S15 Keep away from heat
S33 Take precautionary measures against risk of static discharge
S35 This material and its container must be disposed of in a safe way
S38 In case of insufficient ventilation wear suitable respiratory equipment
S39 Wear eye/face protection

16. OTHER INFORMATION

Comply with manufacturer's installation and maintenance procedures.
Disclaimer:
The information contained herein is accurate to the best knowledge and belief of Fireaway LLC, and is intended to describe the product for health, safety, and environmental requirements only. It is not intended and should not be construed as a warranty. Consult Fireaway LLC for further information.

White Papers

Equipment Exposure

Download PDF

EQUIPMENT EXPOSURE ISSUES FOR Stat-X AEROSOL GENERATORS

Stat-X aerosol has been tested on a wide range of materials including structural, aviation composites, and materials commonly used in electronics, and circuit boards. In all cases it has been shown that Stat-X has no deleterious effect on the operating capability of equipment. 1 2 3

EXTINGUISHING MECHANISM

“Fire propagation” radicals (OH, H, and O) are essential elements in the propagation of the fire. Stat-X suppresses the fire (primarily) by chemical interference with these free radicals within the fire zone – thus interrupting the on-going fire reaction. Potassium radicals (K) are the main active component of Stat-X aerosol. They are very active and react with these “propagation radicals” – much like the bromine radicals did in Halons. The chemical reaction may be represented as follows, for example:

K + OH = KOH
KOH + H = K + H 2 O
K + OH, etc…

In addition, the flame propagation radicals recombine on the surface area of
the ultra-fine aerosol particulate to further interfere with flame propagation:

O + H = OH
H + OH = H 2 O

AEROSOL CHARACTERISTICS

Due to the ultra-fine particle size and the method of generation, the particulate is quite buoyant and suspends in the gas/air mixture within the protected enclosure. Because of this “buoyant” effect the aerosol does not begin to “settle” for an extended period and, therefore, is extremely easy to vent from the protected area. Only very minor amounts of particulate maybe deposited on equipment and, generally, there is no need to do anything beyond extraction of the air within the protected volume through a fan or air

handling system – followed by a blow down with compressed air. Any particulate deposited on horizontal surfaces will be = 2µm and will not form a continuous layer. Large gaps will exist between particles - leaving no potential for electrical conductivity issues to develop.

As a precautionary measure, however, it is always good practice to inspect and clean the site thoroughly following a discharge. While the aerosol itself is quite “clean”, environmental factors are also a consideration. The unknown, and potentially harmful, by-products of an actual fire pose the biggest risk to sensitive electronic equipment. Because unknown products from the fire itself maybe present, it is always recommended that equipment be blown down with air or vacuumed following a discharge to insure that no unwanted by products from the fire itself are present. Unlike HFC's, which can break down and produce deleterious compounds such as hydrofluoric acid when exposed to the high heat of a fire, Stat- X does not break down when exposed to a fire and quickly extinguishes by means of chemical interference with the flame's free radicals. Stat-X has been approved by the United States Environmental Agency (EPA) and approved for use under the EPA's Significant New Alternatives Program (SNAP). 4

Stat-X  AEROSOL COMPOSITION 5

Stat-X aerosol consists of a gas (30%) and solid particulate (70%) mixture.
Mean dimensions of aerosol particulate are in the range of 1-2 µm. The
aerosol consists of the following, primarily, potassium compounds (% mass 90
seconds after discharge) and carrier gases:

Compound: (particulate) % Original Mass
Particulate captured within generator housing during discharge/cooling 30.00
K 2 CO 3 22.08
KHCO 3 3.280
KNO 2 3.160
Other potassium compounds 2.200
NH 4 HCO 3 9.280
Compound: (gas carrier)
N 2 21.93
H 2 O 6.550
CO 2 1.361
CO 0.097
NH 3 0.041
NO 0.001
NO 2 0.002
HCN 0.006
Other Trace
Total 100.00

SUMMARY

Stat-X aerosol has been tested on a wide range of sensitive materials including real world industrial applications. There have been no reports of any negative effects of the aerosol composition on electronic equipment or circuit boards. Properly installed Stat-X systems will not harm electronic equipment and there will be no detrimental affect to the effective life of equipment exposed to Stat-X aerosol.
  1. Findings, Study of Gas Aerosol Fire Extinguishing Compounds on Structural Materials, Maximov, Babkin, Samokhvalova, Report of Metall Company 1991.
  2. Findings, Corrosive Effect of Gas Aerosol Fire Extinguishing Compounds on Structural Materials in Aviation Technology, Leonova G.P., Usankova L.A., Report of All Union Scientific Research Institute for Aviation Materials 1991
  3. Findings, Effect of Gas Aerosol Fire Extinguishing Compounds on Electronic Equipment, Karelin V.G., Antonov, B.I., Scientific Industrial Organization Energia,1991
  4. Authorization letter from US EPA, 2004
  5. 100 ft3 tank testing of Stat-X Fire Suppressant Units, Talley Defense Systems,1999

Environmental and Health Issues for Aerosol Generators

Download PDF

ENVIRONMENTAL ISSUES

There are no environmental issues associated with the use of Stat-X aerosol
generators. Both the Ozone Depletion Potential (ODP) and Global Warming
Potential (GWP) are zero.
Aerosol generators do not present a health hazard in their benign state - as the constituent chemicals are pressed into a solid form that is extremely stable - even at elevated operating temperatures. There are no environmental or health hazards from the chemical in storage.

Unlike gaseous agents, the aerosol does not decompose in the presence of fire

nor does it extinguish by oxygen deprivation. Stat-X suppresses fire (primarily) by chemical interference with the “Fire Propagation” radicals (OH, H, and O) that are essential elements in the expansion of the fire. Stat-X interacts rapidly with these free radicals within the fire zone – thus interrupting the on-going fire reaction.

The aerosol, itself, consists of solid and gas combustion products. The solid phase is composed of highly dispersed particles of salts and oxides of alkaline metals that present insignificant health hazards for humans at normal design concentrations. The gas phase may contain small amounts of carbon monoxide CO, carbon dioxide CO 2 , nitrogen oxides NO X , and ammonia NH 3 . Production of these gases is minimal in the case of Stat-X due to its patented construction, chemical formulation, and its manufacture in the United States using only technical and reagent grade chemicals. In tests conducted by a certified, accredited testing facility in the United States, Stat-X generators were shown to produce gas levels several orders of magnitude less than the standard allowed for automobile airbag systems for passenger vehicles (See Figure 1).

Tests have shown no long-term negative effects from exposure to the aerosol. While the components of the aerosol are not considered toxic at normal concentration levels, ingestion of the ultra-fine particulate may cause shortterm discomfort and unnecessary exposure should be avoided. Studies conducted to date, indicate that any potential toxicological issues with the aerosols in general are related to possible elevated levels of potentially harmful products that may be produced in the gas phase – such as, CO, NOx, etc. - and not due to the influence of the solid particulate. 1,2 In the case of Stat-X , in particular, the effect is negligible due to the extremely low level of gas production (See Figure 1).

In tests conducted by VNIIPO (Russian State Fire Protection Institute), the aerosol was considered to have the same acute toxicity as Halon 13013. The Toxicology Institute of the Public Health and Medical Department of the Russian Federation and tests conducted by the Institute of Biophysics (Department of Public Health and Medicine Russian Federation), as well as others, have shown that the aerosol does not present a health hazard due to limited accidental exposure at normal design concentrations.

Exposure to the aerosol is generally of less concern than is exposure to the decomposition products of a fire. Accidental exposures under five minutes are normally considered safe. Certain safety restrictions, however, should always be observed. Exposure to the aerosol should be avoided as ingestion of the ultrafine particulate may cause short-term discomfort. The discharge of the aerosol also has a relatively high obscuration factor. As a result, the following system installation requirements must be observed.

SYSTEM INSTALLATION REQUIREMENTS

Stat-X total flood systems shall only be applied in occupied areas in conjunction with a 30 second time delay and system isolate switch to insure egress of personnel prior to system discharge and manual only activation whenever personnel may be present in the protected volume.

1 E.A. Smith, E.C. Kimmel , et al, “Toxological Evaluation of Exposure to Two Formulations of a Pyrotechnically-Generated Aerosol: Range Finding and Multiple Dose”, HOTWC.96

2 “Search of Halon Alternatives in Fire Extinguishing” Safety Problems During Emergency Situations, Issue 1-M, 1992, pages 73-79.

3 *Andreev V.A., et al, “Replacement of Halon in Fire Extinguishing Systems”, Proceedings of the Halon Alternatives Technical Working Conference, 1993.

Stat-X Aerosol Physical Properties
Average Values @ 100 gram/m 3 Concentration

Gas Products: (ppm) Stat-X
15 minute TWA*
Automobile- Airbag Emission
Standard
20 minute
TWA*
NIOSH IDLH
NO2 1.08 9.90 20.00
NO 0.97 50.10 100.00
NO X = NO +NO 2 2.05 60.00 120.00
CO 84.20 445.00 1,200.00
CO 2 756.00 40,000.00 40,000.00
NH 3 58.30 151.50 300.00
Solid Particulate Percent
K 2 CO 3 55.2%
KHCO 3 8.2%
KNO2 2 7.9%
Other Potassium Compounds 5.5%
NH 4 HCO 3 23.2%
pH in solution = 8.6  
Particle Size Distribution: Percent
< 1.m 3%
< 2.m 76%
< 5.m 97%
> 5.m 3%
Operating and Storage Conditions:
Humidity Up to 98% @+35°C
Temperature - 54°C to + 54°C
Shelf Life 10 years+
* TWA = Time Weighted Average

Figure 1.0

Electrically Operated Units

Data Sheet

Download PDF

Features

  • Significantly more effective than alternative extinguishing agents
  • Environmentally friendly - Ozone depletion potential (ODP) = 0 - No global warming potential
  • Ease of installation – no pressure vessels, piping, or expensive installation manpower
  • Very low maintenance
  • Provides reliable, cost effective protection for a wide range of fire hazards
  • Tested and Listed to UL Standard 2127 for Class A, B, C fires.
  • Favorably reviewed by EPA for SNAP listing
  • Suitable for enclosed facilities and local applications
  • Safe for personnel - non-harmful to personnel at design application rates
  • Safe for valuable equipment - will not harm electronic equipment or magnetic media
  • Post fire cleanup is minimal - aerosol suspends in air for quick and easy venting after discharge
  • Compact – up to a 90% reduction in space and weight requirements

Applications

Due to their fast response time, low fire extinguishing concentration, and environmental safety, Stat-X fire suppression systems may be used in critical applications across a wide range of industries. Aerosol generators are currently protecting and are suitable for use in:
- Telecommunications facilities - Flammable liquid storage areas
- Process control rooms - Turbine and generator enclosures
- PABX rooms - Marine engine rooms and machinery spaces
- High value mobile equipment - Power plants
- Cellular sites and relay towers - Small boats
- Data processing facilities - General industrial hazards

Operation /Description

Upon detection of a fire, Stat - X generators can be activated either manually or automatically from a suitable listed releasing device. All auxiliary system components (release panel, detection, remote pull stations, etc.) are listed/approved by UL, ULC, FM, New York City MEA, and California State Fire Marshall. Upon activation, the generators produce an exceptionally effective, ultra-fine, potassium based aerosol. Unlike gaseous systems, Stat - X aerosol generators are very cost effective to install and maintain - as they do not require the pressure vessels, piping or expensive installation costs associated with other extinguishing systems. Space and weight requirements are minimal. On an agent weight basis, Stat - X aerosol is ten times more effective than gaseous agent alternatives. The Stat - X generator's effectiveness is a function of its patented design, aerosol composition, and ultra-fine particle size. Fire suppression is rapidly achieved through interference between the ultra-fine aerosol particulate and the flame's free radicals – terminating propagation of the fire. Stat - X aerosol generators are virtually maintenance free and have a service life of over 10 years. This, coupled to their very low installation cost, makes them an extremely cost effective fire protection solution.

General Specifications:

Parameter 30 E 60 E
100 E
250 E
500 E
1000 E 1500 E 2500 E
Aerosol Mass (kg), (lbs) .03 .07 .06 .13 .10 .22 .25 .55 .50 1.10 1.00 2.20 1.50 3.3 2.50 5.50
Ship. Wt./unit packaging (kg), (lbs) 0.36 .8 0.48 1.1 1.44 3.2 2.72 6.0 3.63 8.0 7.05 15.5 8.60 19.0 11.33 25.0
Length (mm), (in) 74 2.9 107 4.2 121 4.8 150 5.9 180 7.1 170 6.7 203 8.0 267 10.5
Diameter (mm), (in) 51 2.0 51 2.0 76 3.0 127 5.0 127 5.0 203 8.0 203 8.0 203 8.0
Discharge Time (sec) 7.0 10.0 12.0 12.0 23.0 16.0 23.0 36.0
Initiation Current
(Amp)
Parallel 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
Series 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Pulse Duration (millisecond) 50 50 50 50 50 50 50 50
Max. Supervisory Current (Amp) = .005 = .005 = .005 = .005 = .005 = .005 = .005 = .005

Coverage Parameters:

Model
Part Number Maximum Volume Coverage Maximum Area Coverage Maximum Mounting Height
(m 3 ) (ft 3 ) (m) (ft) (m) (ft)
30 E 15100 0.45 15.90 1.20 x 1.20 3.95 x 3.95 1.80 6.00
60 E 15110 .90 31.80 1.70 x 1.70 5.60 x 5.60 2.00 6.50
100 E 15120 1.62 57.21 2.18 x 2.18 7.20 x 7.20 2.50 8.20
250 E 15130 4.04 142.7 2.44 x 4.88 8.00 x 16.0 4.50 14.7
500 E 15140 8.08 285.3 4.88 x 4.88 16.0 x 16.0 4.50 14.7
1000 E 15150 16.2 572.1 4.88 x 4.88 16.0 x 16.0 4.88 16.0
1500 E 15160 24.2 854.6 4.88 x 4.88 16.0 x 16.0 4.88 16.0
2500 E 15170 40.4 1426.7 4.88 x 4.88 16.0 x 16.0 4.88 16.0

For additional information on use of Stat-X systems, please contact your local Distributor or Fireaway LLC.

Operation/Storage Parameters:

Temperature -54° C to +54° C (-65° F to +130° F)
Relative Humidity up to 98% at +35° C (+95° F)

Transportation Classification :

  • Classification Code: 1.4S
  • UN Identification #: UN 0432
  • Packaging Group: PGII
  • Shipping Limitations:
    • Ground:   None
    • Max. weight per unit packaging - Cargo Air:   100 kgs (220 lbs)
    • Max. weight per unit packaging - Passenger Air:   25 kgs (55 lbs)

Specifications

Download PDF

Agent Container - The generator housing shall be constructed of exterior and interior stainless steel shells separated by an insulating material. Top and bottom of housing shall be stainless steel and (for electrically activated units) incorporate a ¾” NPT fitting to enable direct connection to conduit. Housing shall be sealed with a non-permeable membrane and shall incorporate a mechanical means to insure rupture of the membrane upon activation. Housing shall be non-pressurized prior to system activation.

Finish - Brushed Stainless Steel. Units shall have passed salt spray corrosion testing per UL Standard 2127 as part of their listing.

Aerosol Agent - Aerosol generated shall be potassium based and manufacturer shall provide fifteen (15) minute time weighted average data from an independent United States laboratory demonstrating that the aerosol does not produce (at normal design concentrations harmful levels of CO, CO2, and NOx based on NIOSH standards. Shall have no ozone depletion potential and no global warming potential. Agent shall be approved for commercial sale by the US EPA.

Listing Aerosol generators shall be listed by Underwriter's Laboratories of Canada to UL Standard 2127 or equivalent.
System - Extinguishing system shall be accomplished by means of distributed generating devices to insure distribution of extinguishing aerosol throughout the protected volume. Devices shall be capable of being supervised.

Mounting - Generator devices shall be mounted by means of stainless steel bracketing that allows for directional adjustment through both vertical and horizontal plane.

Thermal/Manual Units

Data sheet

Download PDF

Features

  • Significantly more effective than alternative extinguishing agents
  • Environmentally friendly - Ozone depletion potential (ODP) = 0 - No global warming potential
  • Ease of installation – no pressure vessels, piping, or expensive installation manpower
  • Very low maintenance
  • Provides reliable, cost effective protection for a wide range of fire hazards
  • No power required – activates thermally or manually
  • Favorably reviewed by EPA for SNAP listing
  • Safe for valuable equipment – will not harm electronic equipment or magnetic media
  • Post fire cleanup is minimal – aerosol suspends in air for quick and easy venting after discharge
  • Compact – up to a 90% reduction in space and weight requirements

Applications

Due to their fast response time, low fire extinguishing concentration, and environmental safety, Stat-X fire suppression systems may be used in critical applications across a wide range of industries. Aerosol generators are suitable for use in:

- Electronic cabinets - Flammable liquid storage
- Switchgear enclosures - Hazmat storage
- CNC machines - Marine engine rooms and machinery spaces
- Data processing equipment - Small boats
- Printing equipment - High value mobile equipment

Operation /Description

In the event of a fire, Stat-X generators can be activated either manually or automatically via the integrated thermal detector. Upon activation, the generators produce an exceptionally effective, ultra-fine, potassium based aerosol. Unlike gaseous systems, Stat-X aerosol generators are very cost effective to install and maintain - as they do not require the pressure vessels, piping or expensive installation costs associated with other extinguishing systems. Space and weight requirements are minimal and, in many applications, the small size of the Stat- X aerosol generators makes them the only viable option. On an agent weight basis, Stat-X aerosol is ten times more effective than gaseous agent alternatives. Fire suppression is rapidly achieved through interference between the ultra-fine aerosol particulate and the flame's free radicals – terminating propagation of the fire. Stat-X aerosol generators are virtually maintenance free and have a shelf life of over 10 years. This, coupled to their very low installation cost, makes them an extremely cost effective fire protection solution.

General Specifications:

Model 30 T 60 T
100 T
250 T
50 T
Aerosol Mass (kg), (lbs) .03 .07 .06 .14 .10 .22 .25 .55 .50 1.10
Ship. Wt./unit packaging (kg), (lbs) .26 .60 .35 .80 3.63 1.44 3.20 6.00 3.63 8.00
Length (mm), (in) 109 4.30 142 5.60 152 6.00 168 6.60 218 8.60
Diameter (mm), (in) 51 2.00 51 2.00 76 3.00 127 5.00 127 5.00
Discharge Time (sec)
Activation Temperature Options 70°C (158°F) 95°C (203°F) 123°C (254°F)
Part Number (Order separately from unit) 14650 14651 14652

Coverage Parameters:

Model
Part Number Aerosol Mass (grams) Maximum Volume Coverage Maximum Area Coverage B/C Maximum Mounting Height
(m 3 ) (ft 3 ) (m 2 ) (ft 2 ) (m) (ft)
30 T 15300 30 0.50 17.66 1.50 16.0 2.0 7.0
60 T 15310 60 1.00 35.32 2.82 30.3 2.5 8.0
100 T 15410 100 1.62 57.21 4.75 51.8 2.5 8.0
250 T 15510 250 4.04 142.7 11.9 128.0 3.0 10.0
500 T 15610 500 8.08 285.3 23.8 256.0 3.0 10.0

For additional information on use of Stat-X systems, please contact your local Distributor or Fireaway LLC.
Operation/Storage Parameters:

Temperature -54° C to +54° C (-65° F to +130° F)
Relative Humidity up to 98% at +35° C (+95° F)

Transportation Classification:

  • Classification Code: 1.4S
  • UN Identification #: UN 0432
  • Packaging Group: PGII
  • Shipping Limitations:
    • Ground:   None
    • Max. weight per unit packaging - Cargo Air:   100 kgs (220lbs)
    • Max. weight per unit packaging - Passenger Air:   25 kgs(55 lbs)
Stat-X is a registered trademark. Manufactured in the USA and sold worldwide exclusively by Fireaway LLC under license from R-Amtech, International.
Made in the USA.
Call to discuss your specific requirements with one of our professionals.

Specifications

Download PDF

Agent Container -The generator housing shall be constructed of exterior and interior steel shells separated by an insulating material. Exterior shell shall be stainless steel. Top and bottom of housing shall be stainless steel and incorporate a fitting to enable direct connection to a Thermal Actuator. Housing shall be sealed with a non-permeable membrane and shall be nonpressurized prior to system activation.

Finish - Brushed Stainless Steel.

Aerosol Agent - Aerosol generated shall be potassium based and manufacturer shall provide fifteen (15) minute time weighted average data from an independent United States laboratory demonstrating that the aerosol does not produce (at normal design concentrations) harmful levels of CO, CO2, and NOx based on NIOSH standards. Agent shall have no ozone depletion potential and no global warming potential. Agent shall be approved for commercial sale by the US EPA.

Thermal Actuator - Unit shall be activated by means of a thermal actuation device rated 70°C, 95°C, or 123°C. Actuator shall be anodized aluminum or stainless steel and shall be capable of both thermal and/or manual activation.